Vizzi Design · SoftPlan Plan Notes & Municipal Redline Prevention Hub

Prepared by @SoftPlan (CAD & Exports) & Guppy · Copy-Ready Sheet Notes + 2:00 PM Williams Deck 14-Correction Prep

1. Today's 2:00 PM Appointment Prep — Jullie Williams ("Williams Deck", 12361 W Muir Ridge Dr, Boise ID)

From Val's (Greenbelt Homes) 9:48 AM email today — Reviewer: Cameron Lennon (City of Boise Planning & Development Services, Cycle 1). Every correction below maps directly to a plan note or sheet callout fix:

Ref # Sheet / File Municipality Correction Comment Exact SoftPlan Note / Drawing Fix to Apply at 2:00 PM
Ref #1–2 Site Plan.pdf Site plan setbacks & lot dimensions / property line distances to proposed deck. Add explicit front, rear, and side yard setback dimensions from deck posts/overhang to property lines + Site Plan Standard Note Block.
Ref #3, #5, #9 Summary.pdf
Eng-Details.pdf
Eng-calculations.pdf
"Update referenced code section to include current adopted codes for the City of Boise." (Flagged in 3 separate places!) Replace Utah code block on Cover Sheet & Engineering Notes with the City of Boise Adopted Code Block (2018 Idaho Residential Code / IRC w/ Boise local amendments, 2018 IECC, 2023 NEC). Copy block below!
Ref #4 Main.pdf (Sheet 2 of 11) "The section view callouts show detail on sheet 2 of 11, this detail isn't provided on sheet 2. Update section view callout or provide detail A on sheet 2 of 11. Update this across all plans to provide consistence and clarity." Update Section Callout bubble on Main.spd so Detail A points to Sheet 6 of 11 (Cross-Section) instead of Sheet 2 of 11, and verify all callout bubbles match actual Plan Set page numbers.
Ref #6 Elevations.pdf "Per City of Boise Design Criteria footing/foundation must be at 24" depth for frost protection. Update for compliance." Ensure all elevation & section footing callouts state: MIN. 24" FROST DEPTH BELOW FINISHED GRADE PER CITY OF BOISE DESIGN CRITERIA (remove any remaining 30" label).
Ref #7 & #14 Main.pdf & General Comment "Provide existing floor plan to show what the original layout of home is and if these are new doors and windows be installed for this project." + "Provide existing floor plan for main and upper floor plan. Provide window and door dimensions." Label all rooms/walls on Main & Upper Floor as (E) EXISTING vs. (N) NEW, turn on window/door dimension labels (e.g., (N) 8'-0" x 8'-0" TEMP. SLIDING GLASS DOOR, (E) 3050 WIN), and add Remodel/Addition Legend Note.
Ref #8 Elevations.pdf "Provide guard rail height and material being used for guard rail per, (R312.1.2)." Add Guardrail Note on Elevations & Section: 36" MIN. GUARDRAIL HEIGHT ABOVE DECK SURFACE PER IRC R312.1.2; METAL/ALUMINUM BALUSTERS SPACED MAX. 4" CLEAR OPENING (4" SPHERE RULE PER R312.1.3); DESIGNED FOR 200 LB CONCENTRATED LOAD.
Ref #10 Plan Review Comment "Provide shear wall engineered plan." Include White Pine Engineering's lateral/shear bracing plan sheet in the combined PDF submittal and add note referencing Structural Shear Wall / Lateral Bracing Sheet.
Ref #11 Eng-calculations.pdf "Provide engineering calculations for footings, foundations and post of deck." Attach Jackson Sagers' (White Pine Engineering) signed deck footing, post, and beam calculation pages (including the approved (3) 1-3/4" x 18" LVL dry-protected beam option or glulam spec).
Ref #12 Cross-section.pdf "Provide drainage information and details for uncovered deck, per (R903.4)." Add Uncovered Deck / Impervious Surface Drainage Note on Cross-Section: UNCOVERED WATERPROOF DECK SURFACE SHALL SLOPE MIN. 1/4" PER FOOT (2%) AWAY FROM STRUCTURE TO EXTERIOR DRAINAGE SCUPPER / GUTTER PER IRC R903.4, WITH CORROSION-RESISTANT METAL FLASHING & COUNTERFLASHING AT WALL INTERSECTION PER R703.4.
Ref #13 Eng-Roof.pdf "Provide glass sliding door and existing header dimension. Provide calculations to show it will adequately support new glass sliding door." Call out exact sliding door rough opening width/height, existing or new header size (e.g., (N) HEADER PER STRUCTURAL CALCS), and add calculation page verifying header load over the new sliding door opening.

2. SoftPlan Code-Review Pass Checklist (Run Before Exporting Any Permit PDF)

Check off these 12 items before exporting a municipal permit set to prevent 95% of Utah & Idaho building department plan-review corrections:

1. Jurisdiction-Matched Code Block & Climatic Table (Cover + Eng): Verify Cover Sheet and Engineering sheets list the exact city/county's adopted IRC/NEC/IECC year and local Frost Depth (e.g., Boise = 24", Utah Valley/SLC = 30", Box Elder/Cache/Mountain = 36"–42"), Ground/Roof Snow Load, Seismic Category, and Wind Speed.
2. Callout & Section Bubble Sheet Cross-References: Verify every Section Cut (`A`, `B`) and Detail Bubble points to the actual sheet number where that section/detail lives in the Plan Set (`Plan Set 1\*.pag`).
3. Remodel / Addition / Deck `(E)` vs. `(N)` Distinction: On any addition, remodel, basement finish, or deck, explicitly show the existing floor plan (`Main` and `Upper`) and label every door and window as `(E) Existing` or `(N) New` with width × height dimensions.
4. Site Plan Completeness & Negative Utility Declaration: Show all 4 property line setbacks, distance between proposed addition/deck and existing structures/garage, driveway width, label all outbuildings, and include an explicit note stating whether well, septic/drain field, or propane tanks exist (or state NONE ON SITE — PUBLIC WATER & SEWER).
5. Guardrail, Handrail & Stair Geometry Note (`IRC R311.7 / R312.1`): Explicitly note guardrail height (`min. 36"`), guardrail material & 4" sphere rule (`R312.1.2–R312.1.3`), stair riser (`max. 7-3/4"`), tread (`min. 10"`), headroom (`6'-8"`), and handrail height (`34"–38"`).
6. Deck / Balcony Drainage & Ledger Flashing (`IRC R903.4 / R507.2`): For any uncovered waterproof deck or covered patio/balcony, call out `1/4" per foot (2%)` drainage slope away from the house, scupper/gutter discharge, and ledger Z-flashing.
7. New Door/Window Header Callouts (`IRC R602.7`): Every new or widened exterior door/sliding glass door or window must label the header size (`(E) Header` or `(N) Engineered Header`) and match the structural calculation sheet.
8. Safety Glazing (`IRC R308.4`) & Egress Windows (`IRC R310`): Label `TEMPERED` on all glazing within 24" of a door arc, within 60" vertically of a tub/shower standing surface, near stairs/landings, or <18" from floor; label `EGRESS` on all sleeping room windows (`5.7 sq ft net clear`).
9. Interconnected Smoke & CO Alarms (`IRC R314 / R315`): Show `SD` in every bedroom + outside sleeping areas + every story, and `CO` outside sleeping areas and on every level with fuel-fired appliances or attached garage.
10. Garage Fire Separation (`IRC R302.5 / R302.6`): Note `1/2" Gypsum Board` on garage walls (`5/8" Type X` on ceilings below habitable rooms), `1-3/8" Solid Wood / Steel OR 20-Min Fire-Rated Self-Closing, Self-Latching Door`, and no HVAC duct penetrations.
11. Electrical AFCI/GFCI/Tamper-Resistant & Ufer Ground (`NEC 210.8 / 210.12 / 250.52`): Include standard NEC electrical code notes on the Electrical sheet so reviewers don't flag missing kitchen island, bath, exterior WP/WR, or concrete-encased electrode specs.
12. Structural Sync Check (Plans vs. Engineering PDF): Confirm footing sizes, frost depth, beam callouts (glulam vs. LVL ply count), and shear wall schedules on architectural sheets match the stamped engineering sheets 100%.

3. Sheet 1 — Cover Sheet / General Code & Climatic Design Criteria Notes

A. Utah Standard Adopted Code Block (2021 IRC / State of Utah)
APPLICABLE CODES (STATE OF UTAH):
• 2021 INTERNATIONAL RESIDENTIAL CODE (IRC) WITH UTAH STATE AMENDMENTS (TITLE 15A)
• 2021 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) WITH UTAH AMENDMENTS
• 2020 / 2023 NATIONAL ELECTRICAL CODE (NFPA 70 / NEC) AS ADOPTED BY STATE OF UTAH
• 2021 INTERNATIONAL PLUMBING, MECHANICAL & FUEL GAS CODES (IPC / IMC / IFGC)

CLIMATIC & GEOGRAPHIC DESIGN CRITERIA (VERIFY SITE-SPECIFIC VALUES WITH AHJ):
• GROUND SNOW LOAD (Pg): [30 / 43 / 50] PSF  |  ROOF SNOW LOAD (Pf): [30 / 35] PSF MIN.
• ULTIMATE WIND SPEED (Vult): 115 MPH (EXPOSURE C)
• SEISMIC DESIGN CATEGORY: [D1 / D2 / E]
• FROST LINE DEPTH: [30" / 36"] MIN. BELOW FINISHED GRADE
• WINTER DESIGN TEMP: [5°F]  |  ICE BARRIER UNDERLAYMENT: REQUIRED (IRC R905.1.2)
• ALLOWABLE SOIL BEARING PRESSURE: 1,500 PSF (UNLESS NOTED IN GEOTECH / STRUCTURAL)
B. City of Boise / Treasure Valley ID Adopted Code Block (Fixes Williams Ref #3, #5, #9, #6)
APPLICABLE CODES (CITY OF BOISE, IDAHO):
• 2018 IDAHO RESIDENTIAL CODE (IRC) WITH CITY OF BOISE LOCAL AMENDMENTS
• 2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) WITH IDAHO AMENDMENTS
• 2023 NATIONAL ELECTRICAL CODE (NEC) WITH IDAHO AMENDMENTS
• 2017 IDAHO STATE PLUMBING CODE & 2018 IMC / IFGC

CITY OF BOISE CLIMATIC & GEOGRAPHIC DESIGN CRITERIA:
• ROOF SNOW LOAD: 25 PSF MIN. (NON-REDUCIBLE)  |  GROUND SNOW LOAD: 20 PSF
• ULTIMATE DESIGN WIND SPEED: 115 MPH (3-SECOND GUST), EXPOSURE B/C
• SEISMIC DESIGN CATEGORY: C
• FROST PROTECTION DEPTH: 24" MINIMUM BELOW FINISHED GRADE
• WEATHERING: SEVERE  |  TERMITE: SLIGHT TO MODERATE  |  WINTER DESIGN TEMP: 10°F
• SOIL BEARING CAPACITY: 1,500 PSF ASSUMED (SEE STRUCTURAL CALCULATIONS FOR FOOTINGS)

4. Sheet 2 — Site Plan Standard Notes (Prevents Setback, Utility & Drainage Redlines)

Standard Site Plan Notes (SoftPlan Site Plan.pag)
SITE PLAN GENERAL NOTES:
1. PROPERTY LINES & SETBACKS: CONTRACTOR SHALL VERIFY ALL PROPERTY CORNERS, MONUMENTS, LOT DIMENSIONS, AND FRONT / REAR / SIDE YARD SETBACKS ON SITE PRIOR TO EXCAVATION. NO FOOTING OR OVERHANG SHALL ENCROACH INTO REQUIRED SETBACKS OR RECORDED UTILITY / DRAINAGE EASEMENTS.
2. EXISTING STRUCTURES & SEPARATION: ALL EXISTING BUILDINGS ON THE LOT ARE LABELED AS (E) HOUSE, (E) DETACHED GARAGE, OR (E) SHED WITH EXACT CLEAR DISTANCE DIMENSIONS SHOWN TO PROPOSED WORK.
3. UTILITIES, WELL, SEPTIC & PROPANE DECLARATION: PROPERTY IS SERVED BY PUBLIC CULINARY WATER, PUBLIC SANITARY SEWER, NATURAL GAS, AND UNDERGROUND ELECTRIC. NO PRIVATE WELL, SEPTIC TANK, DRAIN FIELD, OR PROPANE TANK EXISTS ON SITE (UNLESS EXPLICITLY SHOWN AND DIMENSIONED ON THIS SITE PLAN). CALL 811 (BLUE STAKES / DIGLINE) 48 HOURS PRIOR TO DIGGING.
4. SITE GRADING & SURFACE DRAINAGE (IRC R401.3): FINISH GRADE SHALL SLOPE AWAY FROM ALL FOUNDATION WALLS A MINIMUM OF 6 INCHES WITHIN THE FIRST 10 FEET (5% SLOPE), OR MIN. 2% ON IMPERVIOUS SURFACES. ALL STORM WATER RUNOFF SHALL BE RETAINED ON LOT OR DIRECTED TO APPROVED DRAINAGE SWALES WITHOUT DISCHARGING ONTO ADJACENT PROPERTIES.
5. DRIVEWAY & ACCESS: DRIVEWAY WIDTH ([16'-0" / 20'-0" / 24'-0"]), SLOPE (MAX. 10%–12%), AND CURB CUT / APPROACH SHALL COMPLY WITH MUNICIPAL ENGINEERING STANDARDS.
6. EROSION & SEDIMENT CONTROL (SWPPP): MAINTAIN SILT FENCING, INLET PROTECTION, AND STABILIZED CONSTRUCTION ENTRANCE DURING EXCAVATION AND CONSTRUCTION.
7. STREET ADDRESS NUMBERS (IRC R319.1): 4" MINIMUM HIGH CONTRASTING ADDRESS NUMBERS SHALL BE PERMANENTLY MOUNTED AND CLEARLY VISIBLE FROM THE STREET.

5. Sheet 4 — Main Floor / Floor Plan Standard Notes (Egress, Glazing, Stairs, Fire & Remodel)

A. New Construction & General Floor Plan Notes (SoftPlan Main.pag)
FLOOR PLAN CODE NOTES:
1. EMERGENCY ESCAPE & RESCUE WINDOWS (IRC R310): EVERY BASEMENT AND EVERY SLEEPING ROOM SHALL HAVE AT LEAST ONE OPERABLE EGRESS WINDOW: MIN. 5.7 SQ. FT. NET CLEAR OPENING (5.0 SQ. FT. AT GRADE FLOOR), MIN. 24" NET CLEAR HEIGHT, MIN. 20" NET CLEAR WIDTH, MAX. 44" SILL HEIGHT ABOVE FLOOR. WINDOW WELLS >44" DEEP REQUIRE MIN. 9 SQ. FT. (36" x 36") AREA AND PERMANENT LADDER/STEPS.
2. SAFETY GLAZING IN HAZARDOUS LOCATIONS (IRC R308.4): TEMPERED SAFETY GLAZING IS REQUIRED IN ALL DOORS, WITHIN 24" ARC OF ANY DOOR, WITHIN 60" VERTICALLY OF TUB/SHOWER STANDING SURFACES, ADJACENT TO STAIRS/LANDINGS (<36" ABOVE WALKING SURFACE), AND WHERE GLAZING IS >9 SQ. FT. WITH BOTTOM EDGE <18" ABOVE FLOOR.
3. SMOKE & CARBON MONOXIDE ALARMS (IRC R314 & R315): PROVIDE HARDWIRED, INTERCONNECTED SMOKE ALARMS WITH BATTERY BACKUP IN EACH SLEEPING ROOM, OUTSIDE EACH SLEEPING AREA, AND ON EACH STORY (INCLUDING BASEMENT). PROVIDE INTERCONNECTED CARBON MONOXIDE (CO) ALARMS OUTSIDE EACH SLEEPING AREA AND ON EVERY LEVEL.
4. GARAGE-TO-DWELLING FIRE SEPARATION (IRC R302.5 & R302.6): GARAGE WALLS ADJACENT TO DWELLING SHALL HAVE MIN. 1/2" GYPSUM BOARD; CEILINGS UNDER HABITABLE ROOMS SHALL HAVE MIN. 5/8" TYPE X GYPSUM BOARD SUPPORTED BY MIN. 1/2" GYPSUM ON SUPPORTING WALLS. DOOR BETWEEN GARAGE AND HOUSE SHALL BE 1-3/8" SOLID WOOD/STEEL OR 20-MIN FIRE-RATED WITH SELF-CLOSING, SELF-LATCHING DEVICE. NO HVAC DUCTS OR OPENINGS PERMITTED IN GARAGE.
5. STAIRWAYS, HANDRAILS & GUARDS (IRC R311.7 & R312.1): STAIR WIDTH MIN. 36"; HEADROOM MIN. 6'-8"; MAX. RISER 7-3/4"; MIN. TREAD 10" (W/ 3/4"–1-1/4" NOSING); MAX. VARIANCE 3/8". CONTINUOUS HANDRAIL 34"–38" ABOVE TREAD NOSING ON STAIRS WITH 4 OR MORE RISERS. GUARDS MIN. 36" HIGH WHERE DROP >30" WITH BALUSTERS REJECTING A 4" SPHERE (4-3/8" AT STAIR TRIANGLE).
6. MECHANICAL EXHAUST & ACCESS (IRC M1505 / R807 / R408): BATHROOMS WITHOUT REQUIRED OPERABLE WINDOW SHALL HAVE 50 CFM INTERMITTENT (20 CFM CONTINUOUS) EXHAUST FAN VENTED DIRECTLY TO EXTERIOR. ATTIC ACCESS MIN. 22" x 30"; CRAWLSPACE ACCESS MIN. 18" x 24".
B. Remodel / Addition / Deck Legend Note (Fixes Williams Ref #7, #13, #14)
REMODEL / ADDITION / DECK FLOOR PLAN LEGEND & NOTES:
1. EXISTING VS. NEW DESIGNATION:
   • (E) INDICATES EXISTING ROOMS, WALLS, WINDOWS, DOORS, AND HEADERS TO REMAIN.
   • (N) INDICATES NEW WORK, NEW WALLS, NEW DECK FRAMING, AND NEW WINDOWS/DOORS TO BE INSTALLED UNDER THIS PERMIT.
2. WINDOW & DOOR DIMENSIONS: ALL EXISTING AND NEW EXTERIOR DOORS AND WINDOWS ADJACENT TO THE WORK AREA ARE LABELED WITH WIDTH x HEIGHT DIMENSIONS (E.G., 3050 = 3'-0" x 5'-0"; 8080 SGD = 8'-0" x 8'-0" TEMPERED SLIDING GLASS DOOR).
3. HEADERS OVER NEW OR WIDENED OPENINGS (IRC R602.7): ALL NEW OR MODIFIED EXTERIOR WALL OPENINGS (INCLUDING NEW SLIDING GLASS DOORS) SHALL BE SUPPORTED BY HEADERS, KING STUDS, AND JACK/TRIMMER STUDS SIZED PER THE ATTACHED STRUCTURAL ENGINEERING CALCULATIONS. CONTRACTOR SHALL VERIFY EXISTING HEADER DIMENSIONS AND BEARING PRIOR TO DOOR INSTALLATION.

6. Sheet 4E — Electrical Sheet Standard Notes (NEC 2020/2023 Compliant)

Standard Electrical Sheet Notes (SoftPlan Main Elec.pag)
ELECTRICAL PLAN NOTES (NEC / NFPA 70):
1. TAMPER-RESISTANT & WEATHER-RESISTANT RECEPTACLES (NEC 406.12 & 406.9): ALL 15A AND 20A, 125V/250V DWELLING RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT (TR). EXTERIOR RECEPTACLES AT FRONT/REAR/DECK/PORCH SHALL BE WEATHER-RESISTANT (WR) WITH IN-USE WEATHERPROOF ("BUBBLE") COVERS.
2. GFCI PROTECTION (NEC 210.8(A)): PROVIDE GROUND-FAULT CIRCUIT-INTERRUPTER (GFCI) PROTECTION FOR ALL RECEPTACLES IN BATHROOMS, GARAGES, OUTDOORS, CRAWLSPACES, BASEMENTS (FINISHED & UNFINISHED), KITCHENS (ALL COUNTERTOP & WITHIN 6' OF SINK), LAUNDRY AREAS, AND INDOOR DAMP/WET LOCATIONS.
3. AFCI PROTECTION (NEC 210.12(A)): PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR ALL 120V, 15A AND 20A BRANCH CIRCUITS SUPPLYING OUTLETS OR DEVICES IN KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS, AND SIMILAR ROOMS.
4. WALL & COUNTERTOP RECEPTACLE SPACING (NEC 210.52): WALL RECEPTACLES SHALL BE SPACED SO NO POINT ALONG THE FLOOR LINE IS MORE THAN 6'-0" FROM AN OUTLET (MAX. 12'-0" ON CENTER), INCLUDING ANY WALL SPACE 2'-0" OR WIDER. KITCHEN COUNTERTOPS REQUIRE RECEPTACLES SO NO POINT IS >24" FROM AN OUTLET (20A SMALL-APPLIANCE CIRCUITS, MIN. TWO CIRCUITS).
5. LIGHTING & STAIRWAY SWITCHING (NEC 210.70 & IECC R404.1): PROVIDE AT LEAST ONE WALL-SWITCH-CONTROLLED LUMINAIRE IN EVERY HABITABLE ROOM, KITCHEN, BATHROOM, HALLWAY, STAIRWAY, ATTACHED GARAGE, AND AT EXTERIOR GRADE-LEVEL ENTRANCES. INTERIOR STAIRWAYS WITH 6 OR MORE RISERS REQUIRE 3-WAY WALL SWITCHES AT EACH FLOOR LEVEL. 100% OF PERMANENT LUMINAIRES SHALL BE HIGH-EFFICACY LED.
6. SERVICE PANEL & CONCRETE-ENCASED ELECTRODE / UFER GROUND (NEC 250.52(A)(3)): PROVIDE CONCRETE-ENCASED GROUNDING ELECTRODE (MIN. 20'-0" OF #4 BARE COPPER OR 1/2" REBAR IN BOTTOM OF FOOTING) BONDED TO MAIN SERVICE PANEL.

7. Sheets 3, 5 & 6 — Foundation, Elevations, Cross-Sections & Deck Notes (Fixes Williams Ref #6, #8, #11, #12)

A. Foundation & Footing Notes (SoftPlan Foundation.pag)
FOUNDATION & FOOTING NOTES:
1. STRUCTURAL GOVERNS: ALL FOOTINGS, STEM WALLS, PIER PADS (E.G., SF36), REBAR, ANCHOR BOLTS, HOLD-DOWNS, AND SHEAR WALLS SHALL BE CONSTRUCTED STRICTLY PER THE STAMPED STRUCTURAL ENGINEERING DRAWINGS AND CALCULATIONS INCLUDED IN THIS SUBMITTAL PACKAGE.
2. FROST DEPTH & BEARING (IRC R403.1.4): ALL EXTERIOR FOOTINGS AND DECK PIERS SHALL BEAR ON UNDISTURBED NATURAL SOIL OR ENGINEERED FILL AT OR BELOW THE MUNICIPAL MINIMUM FROST DEPTH ([24" BOISE / 30"–36" UTAH] MIN. BELOW FINISHED GRADE).
3. CONCRETE & REINFORCING: FOUNDATION CONCRETE SHALL BE MIN. 3,000–3,500 PSI @ 28 DAYS WITH REINFORCING STEEL (ASTM A615 GRADE 60) AND 1/2" x 10" ANCHOR BOLTS @ 48"–72" O.C. (WITHIN 12" OF PLATE ENDS/CORNERS) PER STRUCTURAL DETAILS.
4. SILL PLATES (IRC R404 / R317): ALL WOOD SILL PLATES IN CONTACT WITH CONCRETE SHALL BE PRESSURE-TREATED (PT) WITH SILL SEALER GASKET.
B. Elevations, Guardrail & Uncovered Deck Drainage Notes (Fixes Ref #8 & #12)
ELEVATION, GUARDRAIL & DECK DRAINAGE NOTES:
1. GUARDRAIL HEIGHT, MATERIAL & LOAD (IRC R312.1.2 & R312.1.3): PORCH, BALCONY, AND DECK GUARDRAILS SHALL BE MINIMUM 36" IN HEIGHT MEASURED VERTICALLY FROM THE DECK SURFACE, CONSTRUCTED OF [POWDER-COATED ALUMINUM / STEEL / STRUCTURAL WOOD] POSTS AND BALUSTERS SPACED SUCH THAT A 4" DIAMETER SPHERE CANNOT PASS THROUGH ANY OPENING. GUARD SYSTEM AND POST CONNECTIONS SHALL WITHSTAND A 200 LB CONCENTRATED LIVE LOAD APPLIED IN ANY DIRECTION AT THE TOP RAIL.
2. UNCOVERED DECK & ROOF SURFACE DRAINAGE (IRC R903.4): UNCOVERED WATERPROOF DECK MEMBRANE AND WALKING SURFACE SHALL BE SLOPED A MINIMUM OF 1/4" PER FOOT (2% SLOPE) AWAY FROM THE EXISTING BUILDING WALL TOWARD EXTERIOR PERIMETER GUTTER / SCUPPER DRAINS PER IRC R903.4.
3. LEDGER & WALL INTERSECTION FLASHING (IRC R703.4 & R507.2): INSTALL CONTINUOUS CORROSION-RESISTANT METAL Z-FLASHING AND SELF-ADHERING WATERPROOF MEMBRANE AT ALL DECK-TO-WALL AND ROOF-TO-WALL INTERSECTIONS, BEHIND EXTERIOR SIDING/WRB AND OVER LEDGER/FASCIA.
4. MULTI-PLY ENGINEERED LVL / GLULAM BEAMS: WHERE MULTI-PLY LVL BEAMS (E.G., (3) 1-3/4" x 18" LVL) ARE UTILIZED IN LIEU OF SOLID GLULAM PER STRUCTURAL ENGINEER APPROVAL, BEAMS SHALL BE FULLY DRIED-IN / PROTECTED FROM WEATHER AND FASTENED PER STRUCTURAL ENGINEER'S MULTI-PLY CONNECTION SCHEDULE.